Home · Documentation · For designers · ISO-PLA-05

Specification · ISO-PLA-05

Floor over a crawl space — system with studded panels

Suspended foundation — studded panel instead of screed

ISO-PLA-05 — Floor over a crawl space — system with studded panels

1. Subject and scope of application

This specification sets out the technical requirements for quality, execution and acceptance for the build-up “Floor over a crawl space — system with studded panels”, in accordance with Isoflect construction detail ISO-PLA-05. Suspended foundation — studded panel instead of screed.

The specification covers the supply and installation of the Isoflect products in the build-up: Reflectiva Roof Pro, Reflectiva Roof Optim, Isoflect Floor Pro, Isoflect Wolle P800/P1500/P2100 and Isoflect Power Tape. It applies to new constructions and renovations where the design provides for this build-up, and is to be read together with the CAD detail and the technical data sheets of the products.

2. Build-up

Sequence of layers, as per the CAD detail: crawl space → interior.

No.Layer
1Fibre-cement board 12 mm — cold face
2Reflectiva Roof Pro or Roof Optim — diffusion membrane
3C24 timber joists 45 × 240 mm + Isoflect Wolle 240 mm
4OSB 3, tongue and groove, 22 mm
5Isoflect Floor Pro — vapour and radon barrier
6EPS150 studded panel + PE-Xa 16 mm heating coil + 45 mm rough screed
7Finish — softwood floorboards 21 mm

3. Materials and required characteristics

Reflectiva Roof Pro

CharacteristicValueStandard
Build-upMicro-perforated pure aluminium + microporous polypropylene film, heat-bonded, mesh-reinforced structure
Roll dimensions1,50 m × 50 m — 75 m²; 17,5 kgEN 1848-2
Mass per unit area230 g/m²EN 1849-2
Reflectivity of thermal radiation95–97 %
Emissivity (before / after ageing)0,05 / 0,05prEN 15976
Water vapour diffusion resistance, Sd0,045 m (±0,015)EN 12572
Resistance to water penetrationClass W1, including after artificial ageingEN 1928 / EN 13859-1, Annex C
Tensile strength (MD / CMD)350 / 225 N/50 mmEN 12311-1
Tensile strength after ageing (MD / CMD)330 / 175 N/50 mmEN 13859-1, Annex C
Elongation (MD / CMD)30 % / 70 %EN 12311-1
Tear resistance200 / 200 NEN 12310-1
Dimensional stability< 2 %EN 1107-2
Flexibility at low temperatures−30 °CEN 1109
Service temperature range−40 … +80 °C
Reaction to fireClass ESR EN 13501-1
Visible defectsNo visible defectsEN 1850-2
Estimated service life50 years

Reflectiva Roof Optim

CharacteristicValueStandard
Build-up4 layers: outer micro-perforated aluminised foil + three layers of microporous polypropylene film; two integrated self-adhesive strips along the full length
Roll dimensions1,50 m × 50 m — 75 m²; 12 kgEN 1848-2
Mass per unit area155 g/m²EN 1849-2
Emissivity (before / after ageing)0,18 / 0,18prEN 15976
Water vapour diffusion resistance, Sd0,07 m (±0,02)EN 12572
Resistance to water penetrationClass W1, including after artificial ageingEN 1928 / EN 13859-1, Annex C
Tensile strength (MD / CMD)330 / 230 N/50 mm; after ageing 280 / 195EN 12311-1
Elongation (MD / CMD)40 % / 20 %; after ageing 30 % / 10 %EN 12311-1
Tear resistance130 / 140 NEN 12310-1
Dimensional stability< 2 %EN 1107-2
Flexibility at low temperatures−20 °CEN 1109
Service temperature range−40 … +80 °C
Reaction to fireClass ESR EN 13501-1 / EN ISO 11925-2
Estimated service life30 years

Isoflect Floor Pro

CharacteristicValueStandard
Emissivity0,05
Reflectivity of thermal radiation95–97 %
Thermal conductivity, λ₁₀0,0347 W/(m·K)EN 12667
Water vapour diffusion resistance, Sd> 1500 mEN 1931
Total thickness6 mmEN 823
Roll dimensions1 m × 40 m — 40 m²EN 822

The values are those published on the Floor Pro product page; the complete documentation is supplied on request.

Isoflect Wolle

CharacteristicP800P1500P2100Standard
Thickness50 mm100 mm100 mm
Board dimensions1200 × 610 × 50 mm1200 × 610 × 100 mm1200 × 610 × 100 mm
Mass per unit area800 g/m²1500 g/m²2100 g/m²
Pack contents16 boards — 11.712 m²8 boards — 5.856 m²8 boards — 5.856 m²
Thermal conductivity, λ₁₀0,038 W/mK0,038 W/mK0,035 W/mKSR EN 12667:2002
Thermal resistance of the layer, R1,32 m²K/W2,63 m²K/W2,86 m²K/WSR EN 12667:2002
CharacteristicValueStandard
MaterialThermal insulation fibre made of recycled PET, without binders, formaldehyde or phenol
Reaction to fireC-s2,d0EN 13501-1
German classificationB1DIN 4102
Behaviour in the presence of moistureFully hydrophobic
Long-term stabilityNo settlement
Technical approval (Agrément)AT 001SB-03/1039-2024 — INCD URBAN-INCERC, INCERC Bucharest Branch; favourably endorsed by CTPC on 29.01.2025 (Minutes No. 18014); valid until 29.01.2028

Isoflect Power Tape

CharacteristicValueStandard
Width10 cm
Roll length50 m
Service temperature range−60 … +140 °C
Required for Floor ProOne roll for each roll of Floor Pro (40 m²)

The declared values refer to the product, not to the build-up in which it is installed; the performance of the system is determined by a hygrothermal calculation for each case. The current revision of the technical data sheet shall always apply.

Materials in the build-up that are not Isoflect products (timber, boards, metal profiles, roof coverings, waterproofing, screeds, finishes) shall be specified by the designer, in accordance with the applicable product standards and the manufacturers' documentation.

4. Delivery, storage, handling

The products are delivered in their original, labelled packaging, accompanied by the quality documents and, where issued, the declaration of performance. On receipt, the product designation, the roll dimensions or the contents of the package, and the integrity of the packaging are checked.

The Reflectiva Roof Pro and Reflectiva Roof Optim rolls are stored horizontally, on a clean and level surface, protected from the sun.

Isoflect Wolle packages are stored in covered areas, protected from moisture and from direct solar radiation. Handling and cutting do not require conventional protective equipment; the fibre is not irritating.

For Isoflect Floor Pro, the storage conditions are taken from the product documentation, supplied on request.

Isoflect Power Tape is kept in its original packaging, in covered areas, protected from moisture and from direct solar radiation.

The membranes are handled so that the aluminium faces are not perforated or damaged; damaged areas are repaired before the layer is closed.

5. Execution conditions and sequence

Execution begins only after the load-bearing structure has been completed and checked, and the installation surfaces are clean and dry. The layers are executed in the build-up order shown in detail ISO-PLA-05; each layer that is to be covered is checked before being covered. Isoflect products are installed in accordance with the technical data sheets in force.

Isoflect Wolle is installed between the structural elements, in full boards or boards cut to the width of the cavity, without compression and without open joints. The boards are cut with the Wolle Sword knife. In build-ups that also contain a 5 cm layer (P800), this layer is always installed first, before the 10 cm layer, and sits towards the exterior: the first layer installed is self-fixing.

Reflectiva Roof Pro and Reflectiva Roof Optim: fixing is carried out with corrosion-resistant nails or flat-head staples. The strips overlap by approximately 10 cm, so that the integrated self-adhesive strips overlap one another rather than lying side by side. Direct exposure until covering is a maximum of 90 days. The membrane is not installed on surfaces with a temperature above 80 °C. For the floor slab over a crawl space, the membrane is installed on the cold face of the slab, with the aluminium facing downwards, towards the crawl space.

Isoflect Floor Pro is installed on a clean and dry substrate, in the position shown in the detail. Joints are sealed with Isoflect Power Tape — one roll for each roll of Floor Pro, in accordance with the Power Tape data sheet. The Floor Pro installation documentation is supplied on request.

Isoflect Power Tape is applied on a clean, dry and dust-free surface, pressing firmly along the entire length of the joint. Membrane overlaps are covered completely, so that the vapour barrier is continuous; perimeter junctions, penetrations and openings are sealed with the same tape.

6. Checks during execution and at acceptance

On receipt of the materials, the following are checked: the designation and type of the products, in accordance with the design; the current revision of the technical data sheets; the roll dimensions and the contents of the packages; the integrity of the packaging and of the aluminium faces; the declarations of performance, for products that have them; for Isoflect Wolle, technical approval AT 001SB-03/1039-2024 and the declaration of conformity with the approval.

During execution, the following are checked:

  • for Isoflect Wolle: complete filling of the cavities, without compression and without open joints; the layer thickness — the total thickness is not measured; the boards are counted;
  • the order of the Wolle layers: the 5 cm P800 layer installed first;
  • for roof membranes: overlaps of approximately 10 cm, with the self-adhesive strips overlapping and bonded; the fixing; the duration of direct exposure, a maximum of 90 days;
  • for Isoflect Floor Pro: the clean and dry substrate and the sealing of the joints.

Before each layer is covered (plasterboard, OSB, roof boarding, screed, roof covering), a record of concealed works shall be drawn up in accordance with the regulations in force. Acceptance upon completion of the works shall be based on the records of concealed works, the quality documents of the products and the visual inspection of the accessible layers.

7. Measurement and settlement

The Isoflect membranes (Reflectiva Roof Pro, Reflectiva Roof Optim and Isoflect Floor Pro) shall be measured in m² of covered area, as developed, without separate inclusion of the overlaps; overlaps, fixings and technological losses are included in the unit price.

Isoflect Wolle shall be measured in m² of insulated area, separately for each board type (P800, P1500, P2100) and for each layer.

Isoflect Power Tape is included in the unit price of the sealed membrane or is measured separately, in rolls of 50 m, as established in the bills of quantities.

The other layers (structure, profiles, boards, roof coverings, waterproofing, screeds, finishes) shall be measured and settled in accordance with the relevant work chapters.

8. Reference documents

  • Isoflect construction detail ISO-PLA-05 — PDF, DXF and IFC, from the library for designers.
  • Technical data sheet Reflectiva Roof Pro, revision 4, 13.09.2026.
  • Declaration of performance Reflectiva Roof Pro.
  • Technical data sheet Reflectiva Roof Optim, revision 4, 13.09.2026.
  • Declaration of performance Reflectiva Roof Optim.
  • Isoflect Floor Pro documentation, provided on request.
  • Technical data sheet Isoflect Wolle P800, revision 4, 13.09.2026.
  • Technical data sheet Isoflect Wolle P1500, revision 4, 13.09.2026.
  • Technical data sheet Isoflect Wolle P2100, revision 4, 13.09.2026.
  • Declaration of performance Isoflect Wolle P800.
  • Declaration of performance Isoflect Wolle P1500.
  • Declaration of performance Isoflect Wolle P2100.
  • Technical agrément AT 001SB-03/1039-2024 — INCD URBAN-INCERC, INCERC Bucharest Branch; favourably endorsed by CTPC on 29.01.2025 (Minutes No. 18014); valid until 29.01.2028; technical opinion valid until 29.01.2027; declaration of conformity with the technical agrément.
  • Technical data sheet Isoflect Power Tape, revision 4, 13.09.2026.
  • Test standards cited in the technical data sheets: DIN 4102, EN 1107-2, EN 1109, EN 12310-1, EN 12311-1, EN 12572, EN 12667, EN 13501-1, EN 13859-1, EN 1848-2, EN 1849-2, EN 1850-2, EN 1928, EN 1931, EN 822, EN 823, EN ISO 11925-2, SR EN 12667:2002, SR EN 13501-1, prEN 15976.